This case study is part of a project catalogue produced by ReUseHeat to inspire how to utilize excess heat from urban sources for heating and cooling purposes. The catalogue contains 25 existing or planned projects, 12 of which are Danish and 13 from other European countries.
Facts about the case |
|
Installed heat capacity: 160 MW divided amongst four heat pumps (2 x 30 MW and 2x 50 MW) Heat source: Waste water (12°C) Heat pump COP: 3.0 |
Temperatures: Waste water is cooled from 12°C to 3°C. District heating water is heated from 45°C to 75-85°C. Operation hours: A total of 11,496 in 2013, divided amongst the four heat pumps. Period: Established in 1985 |
Description
Four heat pumps extract heat from a wastewater treatment plant at Rya Värmepumpverk in Gothenburg, Sweden. The excess heat is delivered to the local district heating network.
Much of the heating produced in the district heating system of Gothenburg is from excess heat. However, operating other production facilities, such as biomass and natural gas boilers and CHP units, is necessary during winter. To contribute to environmentally friendly heating, the city of Gothenburg established Rya Värmepumpverk, a local heat pump facility with four heat pump units. The heat pump plant was established in 1985 with multiple heat pump units. The units extract heat from the local wastewater treatment plant. The total heating capacity for the heat pumps is 160 MW, divided into two 30 MW heat pumps and two 50 MW heat pumps. All heat pumps are compressor-driven and supplied with electricity from the Swedish grid.
As the heat pumps are greatly flexible, they operate as peak loads. The heat pumps support the baseload in Gothenburg, consisting of waste incineration and heat recovery from a local refinery. The wastewater has temperatures of approximately 12 degrees Celsius, which is cooled to approximately 3 degrees Celsius through the heat pump. The heating delivered to the district heating network is between 75 and 85 degrees Celsius, depending on the season and district heating water is returned at 45 degrees Celsius.
All four heat pumps contain approximately 100 tons of refrigerant R134a. Potential leakages of this, as 1 ton of R134a corresponds to 1430 CO2 equivalents, are the greatest environmental effects of the heat pumps. However, such leakages are uncommon. In 2013, the four heat pumps had 11,496 operation hours, producing 443.0 GWh of heating. All heat pumps operate with a COP just above 3.0.
Gothenburg, Sweden
Established in 1985
IVL Swedish Environmental Research Institute
Names of stakeholders
External links:
Replicability |
Low |
Medium |
High |
---|---|---|---|
Authorizative easiness | x | ||
Adaptability to different climate conditions | x | ||
Technology easy-to-implement (No needs of specific technical requirements) | x | ||
Easy-to-implement (No needs of specific technical requirements) | x | ||
Easy-to-operate (No needs of specific technical requirements) | x | ||
Opportunity of integrating waste energy sources | x | ||
CAPEX needed for the deployment of the solution | x |